Rigid and compact design constructed from aluminum alloy dis-casting capable of operating even in arduous conditions
RLS 300 series are designed suitable for valve and actuators in hazardous area application, having compact but rubust construction conforms to EN50014 and 50018, also suitable in Zone 1 and 2, and ingress protection IP67 Standard aluminum housing provides reliable explosion proof performance.
Technical Specifications |
Enclosure Protection |
Explosion proof Ex d IIC T6 Gb, O-ring |
Ingress Protection |
IP67 (Option IP68) |
Coating |
Epoxy-Polyester outside against corrosion |
(option-Nylon Coating, Special color Coating) |
Area / Gas Group Class |
Zone 1,2 / IIC |
Switches(Sensors) |
2-SPDT mechnical switch(Form C) |
Cable Entries |
2- G 3/4 (Option : 2- M20, M25, NPT3/4) |
Terminal |
8 or 12 nos of terminal strips (6 for switches, 2 for solenoid valve power) |
Position Monitoring Indication |
Dome type 0°~90° |
Switch Rating |
16A 1/2HP 125/250V AC, 0.6A 125V DC, 0.3A 250V DC |
Mounting Bracket |
Stainless Steel acc.to VDI/VCE3845, NAMUR, SS1, SS2, as Standard |
Certification |
KC, IECEX, GOST-RTN, ATEX | | |
 | |